DALI RM8 0-10V PWM
€106,99 Incl. tax €114,13 Incl. tax. Out of stock, but available Manual
Specifications
Information
DALI RM8 0-10V PWM Interface
The DALI RM8 0-10V PWM interface is designed to convert DALI signals into a 0-10V control voltage, enabling the integration of devices with a 0-10V input into a DALI system. This interface offers a comprehensive range of features and specifications for various applications in lighting systems.
Technical Specifications
- Device Type: Signal Converter
- Configurable via DALI Cockpit: Yes
- Operating Temperature: -20°C to +60°C
- Protection Class: IP20
- Connection Wire Cross Section: max. 1.5mm²
- Mounting: Back box installation, integration in luminaires
Electrical Data
- Power Supply: From DALI bus
- DALI Current Consumption: 3mA
- Input: DALI
- Output: 0-100% PWM; max. 2mA
- Relay Switching Voltage: 250V AC / 400V AC
- Relay Nominal Load: 1000VA
- Max. Relay Switching Current: 8A
- Max. Relay Inrush Current: 80A
- Switching Operations at Nominal Load - Resistive: 3x10^4
- Max. Relay Switching Frequency: 1Hz
Available Types and Colors
- Color: Grey
- Types:
- RM8 0-10V PWM
- RM8 1-10V
- RM16 1-10V
- RM16 0-10V PWM
Functions
The interface converts the desired DALI dim level into a corresponding PWM pattern or analog output voltage. From firmware version 2.0, device type 5 is supported, allowing for both linear and logarithmic control characteristics. For the PWM types, the output range can be selected between 0-10V and 1-10V. The DALI value [0-254] is converted linearly or logarithmically to the output range.
The SPST relay is directly linked to the 8-bit direct arc power level. If the value is 0, the relay is OFF; at any other value [1…254], the relay is ON. The combination of the 0-10V control signal and the additional SPST relay offers the possibility to power on/off the mains supply of the 0-10V controlled electronic ballast.
In case of a system failure, 100% (10V) is applied to the 0-10V control output. The relay's behavior depends on the firmware version. In any case, the relay holds the output state. In newer versions, the system failure level can be set. The relay can be switched on or off or set to hold the current state (option available from FW 3.5.0 at 86458667-DE, from FW 3.3.0 at 86458668, and from FW 1.3.0 at 86458668-AN).